• Illumination emergency power supply (single input/single output/triple input/triple output)
Illumination emergency power supply (single input/single output/triple input/triple output)
+

Share

Illumination emergency power supply (single input/single output/triple input/triple output)

Using advanced DSP control, the product is reliable and stable, and achieves digital control.

Still deciding? If you are interested, you need to take a sample first,Contact us!

Product Category

Tag

Charging pile

Power industry

  • Product Description
  • Technical Features
     

    1. Adopts advanced DSP control, making the product reliable and stable, and realizing digital control;

     

    2. Full Chinese (English optional) real-time display of ESP's working status and running parameters, intuitive, convenient, and easy to operate;

    3. Complete battery management function, with automatic equalization charging to floating charging, regular battery detection, single-cell battery voltage display, and battery fault alarm functions, making the EPS battery life longer;

     
     
     

    4. Adopts power frequency transformer isolation output, has strong load adaptability, good impact resistance, and high reliability, and is suitable for power supply of any type of load;

     

    5. Has dry contact remote monitoring and control functions and linkage control with other devices (optional);

     

    6. Intelligent fan control makes the unit noise low and has a long service life;

     

    7. Automatic switching, unattended operation can be achieved, the switching time between the power grid and the EPS power supply is less than 0.1 seconds, meeting all emergency power supply needs;

    8. Using utility power bypass and inverter backup power supply, the efficiency is >99% under utility power conditions, saving electricity for users, and consuming almost no power during non-emergency power supply;

     
     
     

    9. Has a dual utility power automatic transfer function, detecting the presence or absence of main and backup power and automatically switching;

     

    10. Has RS232, SNP (optional), single-machine, and network management communication functions, enabling the product to achieve intelligence.

    S Series Technical Parameters
    Model (FSE-KW/S) 0.5KW 1~4KW 5~20KW
    Input Specifications Input Method L+N+PE or A+B+C+N+PE
    Input Voltage and Frequency
    220VAC/50HZ or 380VAC/50HZ
    Input Voltage Range 165VAC-265VAC or 285VAC-459VAC
    Output Specifications
    Emergency Output Voltage Type
    Sine Wave AC
    Utility Power Output Voltage
    Same as Utility Power
    Emergency Output Voltage 220V±2%
    Power Failure to Emergency Power Transfer Time
    <0.1S
    DC System
    Nominal Voltage
    48VDC 192VDC
    Emergency Working Time
    Battery capacity is configured according to customer needs
    Overall Specifications
    Utility Power Efficiency
    >92%
    >98%
    Emergency Efficiency
    >80% >85% >87%
    Display Method
    LCD+LED
    Display Accuracy
    ±2%
    Other Functions
    Overload Characteristics
    <120% normal operation; >125% 10S delay protection;
    Dual Power Switching Function
    The machine has a built-in dual power switch, inputting main and backup power, and automatically switching
    Automatic Recovery Function Upon Power Restoration After the battery discharges to low-voltage protection, if the main power is restored, the EPS can start normally